KWL802 Split-Type Radar Level Sensor
1.Introduction
1.1 Product Overview
KWL802 radar level sensor conforms to the standard specifications outlined in national standard DB50/T 826-2017 for level meters. Its core component is designed with a fully sealed IP68 waterproofing.
The maximum measurement range of the product extends up to 40 meters, with a minimal blind spot of less than 6 cms.
Due to its higher frequency and broader bandwidth, it achieves superior accuracy. Additionally, the product includes a fixed bracket for installation.
1.2 Detection principle
Radar level sensor is based on the principle of time domain reflection (TDR). The electromagnetic pulse propagates along the cable or probe with the speed of light. When it meets the surface of the measured medium, part of the pulse of the radar level meter is reflected to form an echo return to the pulse transmitter along the same path, and the distance between the transmitter and the surface of the measured medium is In direct proportion as the propagation time of the pulse, hence the height of the level is calculated.
2.Feature
- Based on the self-developed CMOS millimeter-wave RF chip
- More compact RF architecture
- Higher signal-to-noise ratio
- Smaller dead zone
- 5GHz working bandwidth
- Higher measurement resolution and measurement accuracy
- Less influence by the interference in the installation environment
- More convenient of installation and
- Modern design of integrated flat antenna
3.Wiring Instructions
3.1 [RS485 version] Wiring instructions
| Red line | VCC (9~24V power supply) |
| Black line | GND |
| Yellow line | 485-A |
| Green line | 485-B |
3.2 [RS232 version] Wiring instructions
| Red line | 12 (6~28V power supply) |
| Black line | GND |
| Yellow line | TX |
| Green line | RX |
3.3 [TTL version] Wiring instructions
| Red line | VCC |
| Black line | GND |
| Yellow line | TX |
| Green line | RX |
| Model | KWL802-RS485 KWL802-RJ45 KWL802-RS232 KWL802-TTL |
|---|---|
| Frequency of measurement | 80GHz |
| Communication | RS485 |
| Frequency of acquisition | ≥200ms/ configurable |
| Current of operation | 12V/14mA |
| Distance measurement accuracy | ±2mm |
| Communication protocol | Modbus/ Text protocol |
| Antenna beam width | ±2.75° |
| Supply voltage | 9~24V |
| Range of measurement | 0.2~40m 0.18~30m 0.1~15/20m 0.06~3/5/10m |
| RF pulse current | 100mA/20ms |
| Working humidity | 0~95% |
| Type of thread | G thread/ customized |
| Working temperature | -40~75℃ |
| Grade of water resistance | IP68 |
| Net weight | 0.6kgs |
Related Articles View