1. Project Background

Located in a chemical plant in Jiangsu Province, China, this project involves a methanol refining and transfer system. Crude methanol from storage tanks passes through a degassing tower to remove dissolved gases, producing pure liquid methanol, which is then delivered to downstream reaction processes.

KUF100B Ultrasonic Flow Meter in Methanol Refining and Transfer System (3)

2. Site Conditions

  • Pipe size: DN150 carbon steel
  • Medium: Degassed pure methanol
  • Installation: External clamping, no pipe cutting
  • Environment: Flammable and volatile medium, equipped with explosion-proof enclosure
  • Purpose: Process flow monitoring and automation system data acquisition

Measured data example:

  • Average flow: 3.2 m³/h, peak flow: up to 4.5 m³/h

The system continuously monitors methanol flow to track pump performance, recirculation, and transport stability.

3. System Configuration and Advantages

  • Model: KUF100B
  • Measurement principle: Ultrasonic transit-time, non-contact
  • Output: RS485 (Modbus RTU)
  • Installation advantage: External clamping, no pipeline modification required
  • Safety: Explosion-proof enclosure ensures safe operation in flammable environments
  • Accuracy: ±1%, sufficient for process control and trend monitoring

4. Installation and Commissioning

  1. Mount the ultrasonic sensor on the external pipe wall with proper acoustic coupling
  2. Test signal stability and RS485 communication with automation system
  3. Verify explosion-proof enclosure functionality
  4. Commission and start continuous monitoring without disrupting production
KUF100B Ultrasonic Flow Meter in Methanol Refining and Transfer System (2)
KUF100B Ultrasonic Flow Meter in Methanol Refining and Transfer System (1)

5. Performance

  • Stable data: Flow readings consistent with pump operation
  • Safety ensured: Non-contact installation plus explosion-proof enclosure
  • Effective process control: Supports automation feedback and trend analysis
  • Low maintenance: Easy installation, long-term operation requires minimal maintenance

Statistics after 6 months of operation: Flow measurements matched pump records closely, ±1% accuracy met process control requirements, with no abnormal alarms or leaks.

6. Summary